Table 479: MPDIF Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Slope section 3
10...100
%
1
100
Slope of the third
line of the operat-
ing characteristics
DC restrain enable
0=False
1=True
0=False
Setting for ena-
bling DC restrain
feature
Table 480: MPDIF Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
CT connection type 1=Type 1
2=Type 2
1=Type 1
CT connection
type. Determined
by the directions of
the connected cur-
rent transformers
CT ratio Cor Line
0.40...4.00
0.01
1.00
CT ratio correction,
line side
CT ratio Cor Neut
0.40...4.00
0.01
1.00
CT ratio correction,
neutral side
4.3.1.8
Monitored data
Table 481: MPDIF Monitored data
Name
Type
Values (Range)
Unit
Description
OPR_A
BOOLEAN
0=False
1=True
Operate phase A
OPR_B
BOOLEAN
0=False
1=True
Operate phase B
OPR_C
BOOLEAN
0=False
1=True
Operate phase C
INT_BLKD_A
BOOLEAN
0=False
1=True
Internal block status
phase A
INT_BLKD_B
BOOLEAN
0=False
1=True
Internal block status
phase B
INT_BLKD_C
BOOLEAN
0=False
1=True
Internal block status
phase C
ID_A
FLOAT32
0.00...80.00
xIr
Differential current
phase A
ID_B
FLOAT32
0.00...80.00
xIr
Differential current
phase B
ID_C
FLOAT32
0.00...80.00
xIr
Differential current
phase C
IB_A
FLOAT32
0.00...80.00
xIr
Biasing current phase A
IB_B
FLOAT32
0.00...80.00
xIr
Biasing current phase B
IB_C
FLOAT32
0.00...80.00
xIr
Biasing current phase C
I_ANGL_A1_B1
FLOAT32
-180.00...180.00
deg
Current phase angle
phase A to B, line side
Table continues on the next page
1MRS757644 H
Protection functions
620 series
Technical Manual