14.5
Binary inputs
Table 1089: Binary inputs
Description
Value
Operating range
±20% of the rated voltage
Rated voltage
24...250 V DC
Current drain
1.6...1.9 mA
Power consumption
31.0...570.0 mW
Threshold voltage
16...176 V DC
Reaction time
<3 ms
Adjust the binary input threshold voltage correctly. The threshold voltage
should be set to 70% of the nominal auxiliary voltage. The factory default
is 16 V to ensure the binary inputs’ operation regardless of the auxiliary
voltage used (24, 48, 60, 110, 125, 220 or 250 V DC). However, the
default value is not optimal for the higher auxiliary voltages. The binary
input threshold voltage should be set as high as possible to prevent
any inadvertent activation of the binary inputs due to possible external
disturbances. At the same time, the threshold should be set so that
the correct operation is not jeopardized in case of undervoltage of the
auxiliary voltage.
Technical data
1MRS757644 H
1196