4.3.4.9
Signals
Table 502: HREFPDIF Input signals
Name
Type
Default
Description
IDo
SIGNAL
0
Differential current
BLOCK
BOOLEAN
0=False
Block signal for activating the
blocking mode
Table 503: HREFPDIF Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
4.3.4.10
Settings
Table 504: HREFPDIF Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operate value
1.0...50.0
%In
0.1
1.0
Low operate value,
percentage of the
nominal current
Minimum operate
time
40...300000
ms
1
40
Minimum operate
time
Table 505: HREFPDIF Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 506: HREFPDIF Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
4.3.4.11
Monitored data
Table 507: HREFPDIF Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time / op-
erate time
HREFPDIF
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS757644 H
Protection functions
620 series
Technical Manual