Figure 158: Phasors in a single-phase earth fault, phases A-N, and two-phase short
circuit, phases B and C, when the actuating polarizing quantity is the negative-
sequence voltage -U2
Positive sequence voltage as polarizing quantity
Table 299: Equations for calculating angle difference for positive-sequence quan-
tity polarizing method
Faulted
phases
Used
fault
current
Used
polarizing
voltage
Angle difference
A
I
A
U
1
ANGLE
A
U
I
A
RCA
_
(
)
(
)
=
−
−
ϕ
ϕ
ϕ
1
B
I
B
U
1
ANGLE
B
U
I
B
RCA
_
(
)
(
)
=
−
−
−
ϕ
ϕ
ϕ
1
120
o
C
I
C
U
1
ANGLE
C
U
I
C
RCA
_
(
)
(
)
=
−
−
+
ϕ
ϕ
ϕ
1
120
o
A - B
I
A
- I
B
U
1
ANGLE
A
U
I
I
A
B
RCA
_
(
)
(
)
=
−
−
−
+
ϕ
ϕ
ϕ
1
30
o
B - C
I
B
- I
C
U
1
ANGLE
B
U
I
I
B
C
RCA
_
(
)
(
)
=
−
−
−
−
ϕ
ϕ
ϕ
1
90
o
C - A
I
C
- I
A
U
1
ANGLE
C
U
I
I
C
A
RCA
_
(
)
(
)
=
−
−
−
+
ϕ
ϕ
ϕ
1
150
o
1MRS757644 H
Protection functions
620 series
Technical Manual
313