Parameter
Values (Range)
Unit
Step
Default
Description
Voltage level 5
0.00...1.20
xUn
0.01
0.90
5th voltage coordi-
nate for defining
LVRT curve
Voltage level 6
0.00...1.20
xUn
0.01
0.90
6th voltage coordi-
nate for defining
LVRT curve
Voltage level 7
0.00...1.20
xUn
0.01
0.90
7th voltage coordi-
nate for defining
LVRT curve
Voltage level 8
0.00...1.20
xUn
0.01
0.90
8th voltage coordi-
nate for defining
LVRT curve
Voltage level 9
0.00...1.20
xUn
0.01
0.90
9th voltage coordi-
nate for defining
LVRT curve
Voltage level 10
0.00...1.20
xUn
0.01
0.90
10th voltage coor-
dinate for defining
LVRT curve
Recovery time 1
0...300000
ms
1
500
1st time coordinate
for defining LVRT
curve
Recovery time 2
0...300000
ms
1
1000
2nd time coordi-
nate for defining
LVRT curve
Recovery time 3
0...300000
ms
1
10000
3rd time coordi-
nate for defining
LVRT curve
Recovery time 4
0...300000
ms
1
10000
4th time coordi-
nate for defining
LVRT curve
Recovery time 5
0...300000
ms
1
10000
5th time coordi-
nate for defining
LVRT curve
Recovery time 6
0...300000
ms
1
10000
6th time coordi-
nate for defining
LVRT curve
Recovery time 7
0...300000
ms
1
10000
7th time coordinate
for defining LVRT
curve
Recovery time 8
0...300000
ms
1
10000
8th time coordi-
nate for defining
LVRT curve
Recovery time 9
0...300000
ms
1
10000
9th time coordi-
nate for defining
LVRT curve
Recovery time 10
0...300000
ms
1
10000
10th time coordi-
nate for defining
LVRT curve
4.5.9.8
Monitored data
Table 652: LVRTPTUV Monitored data
Name
Type
Values (Range)
Unit
Description
LVRTPTUV
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Protection functions
1MRS757644 H
694
620 series
Technical Manual