Name
Type
Description
PROT_CRD
BOOLEAN
A signal for coordination between
the AR and the protection
UNSUC_RECL
BOOLEAN
Indicates an unsuccessful reclosing
sequence
AR_ON
BOOLEAN
Autoreclosing allowed
READY
BOOLEAN
Indicates that the AR is ready for
a new sequence, i.e. the CB_READY
input equals TRUE
ACTIVE
BOOLEAN
Reclosing sequence is in progress
9.4.8
Settings
Table 1008: DARREC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off/On
Reclosing opera-
tion
1=Off
2=External Ctl
3=On
1=Off
Reclosing opera-
tion (Off, External
Ctl / On)
Close pulse time
10...10000
ms
10
200
CB close pulse time
Reclaim time
100...1800000
ms
100
10000
Reclaim time
Terminal priority
1=None
2=Low (follower)
3=High (master)
1=None
Terminal priority
Synchronisation
set
0...127
1
0
Selection for syn-
chronizing require-
ment for reclosing
Auto initiation cnd 1=Not allowed
2=When sync fails
3=CB doesn't close
4=Both
2=When sync fails
Auto initiation con-
dition
Tripping line
0...63
1
0
Tripping line,
defines INIT in-
puts which cause
OPEN_CB activa-
tion
Fourth delay in
SOTF
0=False
1=True
0=False
Sets 4th delay into
use for all DEL_IN-
IT signals during
SOTF
First reclose time
0...300000
ms
10
5000
Dead time for CBB1
Second reclose
time
0...300000
ms
10
5000
Dead time for CBB2
Third reclose time
0...300000
ms
10
5000
Dead time for CBB3
Fourth reclose time 0...300000
ms
10
5000
Dead time for CBB4
Fifth reclose time
0...300000
ms
10
5000
Dead time for CBB5
Sixth reclose time
0...300000
ms
10
5000
Dead time for CBB6
Seventh reclose
time
0...300000
ms
10
5000
Dead time for CBB7
Table continues on the next page
Control functions
1MRS757644 H
1040
620 series
Technical Manual