Name
Type
Default
Description
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
RELEASE
BOOLEAN
0=False
External trigger to re-
lease neutral admit-
tance protection
RESET
BOOLEAN
0=False
External trigger to re-
set direction calcula-
tion
Table 469: MFADPSDE Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
BLK_EF
BOOLEAN
Block signal for EF to indicate
opposite direction peaks
INTR_EF
BOOLEAN
Intermittent earth-fault indi-
cation
PEAK_IND
BOOLEAN
Current transient detection
indication
4.2.8.7
Settings
Table 470: MFADPSDE Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Directional mode
2=Forward
3=Reverse
2=Forward
Directional mode
Voltage start value 0.01...1.00
xUn
0.01
0.10
Voltage start value
Operate delay time 60...1200000
ms
10
500
Operate delay time
Table 471: MFADPSDE Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Operating quantity 1=Adaptive
2=Amplitude
1=Adaptive
Operating quantity
selection
Min operate cur-
rent
0.005...5.000
xIn
0.001
0.010
Minimum operate
current
Tilt angle
2.0...20.0
deg
0.1
5.0
Characteristic tilt
angle
1MRS757644 H
Protection functions
620 series
Technical Manual
499