Table 643: OEPVPH Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Mode
Off / On
Cooling time
5...10000
s
1
600
Time required to
cool the machine
Constant delay
100...120000
ms
10
800
Parameter con-
stant delay
Maximum operate
time
500000...10000000 ms
10
1000000
Maximum operate
time for IDMT
curves
Voltage selection
1=phase-to-earth
2=phase-to-phase
3=pos sequence
3=pos sequence
Selection of
phase / phase-to-
phase / pos se-
quence voltages
Phase selection
1=A or AB
2=B or BC
3=C or CA
1=A or AB
Parameter for
phase selection
Leakage React
0.0...50.0
%
0.1
0.0
Leakage reactance
of the machine
Voltage Max Cont
80...160
%
1
110
Maximum allowed
continuous operat-
ing voltage ratio
Table 644: OEPVPH Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
10
100
Resetting time of
the operate time
counter in DT mode
Minimum operate
time
200...60000
ms
10
200
Minimum operate
time for IDMT
curves
4.5.8.9
Monitored data
Table 645: OEPVPH Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time / op-
erate time (in %)
T_ENARESTART
INT32
0...10000
s
Estimated time to reset
of block restart
VOLTPERHZ
FLOAT32
0.00...10.00
pu
Excitation level, i.e U/f
ratio or Volts/Hertz
OEPVPH
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Protection functions
1MRS757644 H
686
620 series
Technical Manual