4.2.4.7
Signals
Table 436: EFPADM Input signals
Name
Type
Default
Description
Io
SIGNAL
0
Residual current
Uo
SIGNAL
0
Residual voltage
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
RELEASE
BOOLEAN
0=False
External trigger to re-
lease neutral admit-
tance protection
Table 437: EFPADM Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
4.2.4.8
Settings
Table 438: EFPADM Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Voltage start value 0.01...2.00
xUn
0.01
0.15
Voltage start value
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward
Directional mode
Operation mode
1=Yo
2=Go
3=Bo
4=Yo, Go
5=Yo, Bo
6=Go, Bo
7=Yo, Go, Bo
1=Yo
Operation criteria
Operate delay time 60...200000
ms
10
60
Operate delay time
Circle radius
0.05...500.00
mS
0.01
1.00
Admittance circle
radius
Circle conductance -500.00...500.00
mS
0.01
0.00
Admittance circle
midpoint, conduc-
tance
Circle susceptance -500.00...500.00
mS
0.01
0.00
Admittance circle
midpoint, suscep-
tance
Conductance for-
ward
-500.00...500.00
mS
0.01
1.00
Conductance
threshold in for-
ward direction
Conductance re-
verse
-500.00...500.00
mS
0.01
-1.00
Conductance
threshold in re-
verse direction
Table continues on the next page
Protection functions
1MRS757644 H
452
620 series
Technical Manual