Table 263: PH3IPTOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Num of start pha-
ses
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases
required for oper-
ate activation
Table 264: PH3IPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
10
20
Reset delay time
4.1.2.9
Monitored data
Table 265: PH3LPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time / op-
erate time
PH3LPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 266: PH3HPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time / op-
erate time
PH3HPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 267: PH3IPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time / op-
erate time
PH3IPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Protection functions
1MRS757644 H
272
620 series
Technical Manual