Table 847: CTSRCTF Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Min operate cur-
rent
0.01...0.50
xIn
0.01
0.02
Minimum operate
current
Max operate cur-
rent
1.00...5.00
xIn
0.01
1.30
Maximum operate
current
Max Ng Seq current 0.01...1.00
xIn
0.01
0.10
Maximum I2 cur-
rent in healthy set
6.3.8
Monitored data
Table 848: CTSRCTF Monitored data
Name
Type
Values (Range)
Unit
Description
INT_BLKD
BOOLEAN
0=False
1=True
Function blocked inter-
nally
CTSRCTF
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
6.3.9
Technical data
Table 849: CTSRCTF Technical data
Characteristic
Value
Operate time
1
<30 ms
1
Including the delay of the output contact
Supervision functions
1MRS757644 H
890
620 series
Technical Manual