Warning indication
Warning code Additional information
SMV Warning
34
Error in the SMV configuration
Warning
Comm. channel down
35
Redundant Ethernet (HSR/PRP) communica-
tion interrupted.
Warning
Unack card comp.
40
A new composition has not been acknowl-
edged/accepted.
Warning
Protection comm.
50
Error in protection communication.
Warning
ARC1 cont. light
85
A continuous light has been detected on the
ARC light input 1.
Warning
ARC2 cont. light
86
A continuous light has been detected on the
ARC light input 2.
Warning
ARC3 cont. light
87
A continuous light has been detected on the
ARC light input 3.
Warning
RTD card error,X105
90
Temporary error occurred in RTD card loca-
ted in slot X105
Warning
RTD card error,X110
94
Temporary error occurred in RTD card loca-
ted in slot X110
Warning
RTD card error,X130
96
Temporary error occurred in RTD card loca-
ted in slot X130.
Warning
RTD meas. error,X105
100
Measurement error in RTD card located in
slot X105.
Warning
RTD meas. error,X110
104
Measurement error in RTD card located in
slot X110.
Warning
RTD meas. error,X130
106
Measurement error in RTD card located in
slot X130.
For further information on warning indications, see the operation manual.
3.2.3
Fail-safe principle for relay protection
The relay behavior during an internal fault situation has to be considered when
engineering trip circuits under the fail-safe principle. The considerations discussed
and examples given are mainly based on the need of protection scheme reliability.
The reliability need can be divided into two subparts: dependability and security.
The dependability can be described as the protection scheme’s ability to operate
when required. The security can be described as the protection scheme’s ability to
refrain from operating when not required. The protection scheme fail-safe principle
Basic functions
1MRS757644 H
76
620 series