14.10
Signal/trip output with high make and carry and
with TCS function
Table 1094: Signal/trip output with high make and carry and with TCS function
Description
Value
1
Rated voltage
250 V AC/DC
Continuous contact carry
5 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit
time constant L/R < 40 ms, at 48/110/220
V DC (two contacts connected in series)
1 A/0.25 A/0.15 A
Minimum contact load
100 mA at 24 V AC/DC
1
X130: SO3 of RET620 equipped with RTD0002
1MRS757644 H
Technical data
620 series
Technical Manual