4.2.2.14
Technical revision history
Table 425: DEFHPDEF Technical revision history
Technical revision
Change
B
Maximum value changed to 180 deg for the
Max forward angle setting
C
Added a setting parameter for the "Meas-
ured Io" or "Calculated Io" selection and set-
ting parameter for the "Measured Uo", "Cal-
culated Uo" or "Neg. seq. volt." selection for
polarization.
Operate delay time
and
Mini-
mum operate time
changed from 60 ms to
40 ms. The sector default setting values are
changed from 88 degrees to 80 degrees.
D
Step value changed from 0.05 to 0.01 for the
Time multiplier
setting.
E
Unit added to calculated operating current
output (I_OPER).
F
Added setting
Pol quantity
.
Table 426: DEFLPDEF Technical revision history
Technical revision
Change
B
Maximum value changed to 180 deg for the
Max forward angle
setting.
Start value
step changed to 0.005
C
Added a setting parameter for the "Meas-
ured Io" or "Calculated Io" selection and set-
ting parameter for the "Measured Uo", "Cal-
culated Uo" or "Neg. seq. volt." selection for
polarization. The sector default setting val-
ues are changed from 88 degrees to 80 de-
grees.
D
Step value changed from 0.05 to 0.01 for the
Time multiplier
setting.
E
Unit added to calculated operating current
output (I_OPER).
F
Added setting
Pol quantity
. Minimum value
for
Operate delay time
and
Minimum operate
time
changed from “60 ms” to “50 ms”. De-
fault value for
Operate delay time
and
Mini-
mum operate time
changed from “60 ms” to
“50 ms”.
4.2.3
Transient-intermittent earth-fault protection INTRPTEF
1MRS757644 H
Protection functions
620 series
Technical Manual
419