![ABB Relion 620 Series Technical Manual Download Page 105](http://html.mh-extra.com/html/abb/relion-620-series/relion-620-series_technical-manual_2838045105.webp)
Name
Type
Values (Range)
Unit
Description
-103=MAPGAPC13
-76=MAPGAPC18
-75=MAPGAPC17
-62=SRCPTOC1
-74=DOPPDPR3
-73=DOPPDPR2
-70=DUPPDPR2
-58=UZPDIS1
-36=UEXPDIS1
14=MFADPSDE1
-10=LVRTPTUV1
-8=LVRTPTUV2
-6=LVRTPTUV3
-122=DPH3LPDOC1
-121=DPH3HPDOC2
-120=DPH3HPDOC1
-119=PH3LPTOC2
-118=PH3LPTOC1
-79=PH3HPTOC2
-78=PH3HPTOC1
-77=PH3IPTOC1
-127=PHAPTUV1
-124=PHAPTOV1
-123=DPH3LPDOC2
-68=PHPVOC2
-67=DQPTUV2
-39=UEXPDIS2
98=MHZPDIF1
-4=MREFPTOC1
Start duration
FLOAT32
0.00...100.00
%
Maximum start dura-
tion of all stages during
the fault
Operate time
FLOAT32
0.000...999999.999
s
Operate time
Breaker clear time
FLOAT32
0.000...3.000
s
Breaker clear time
Fault distance
FLOAT32
0.00...3000.00
pu
Distance to fault meas-
ured in pu
Fault resistance
FLOAT32
0.00...1000000.00
ohm
Fault resistance
Active group
INT32
1...6
Active setting group
Shot pointer
INT32
1...7
Autoreclosing shot
pointer value
Max diff current IL1
FLOAT32
0.000...80.000
pu
Maximum phase A dif-
ferential current
Max diff current IL2
FLOAT32
0.000...80.000
pu
Maximum phase B dif-
ferential current
Max diff current IL3
FLOAT32
0.000...80.000
pu
Maximum phase C dif-
ferential current
Diff current IL1
FLOAT32
0.000...80.000
pu
Differential current
phase A
Diff current IL2
FLOAT32
0.000...80.000
pu
Differential current
phase B
Diff current IL3
FLOAT32
0.000...80.000
pu
Differential current
phase C
Max bias current IL1
FLOAT32
0.000...50.000
pu
Maximum phase A bias
current
Table continues on the next page
1MRS757644 H
Basic functions
620 series
Technical Manual
105