Table 472: MFADPSDE Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Operation mode
1=Intermittent EF
3=General EF
4=Alarming EF
3=General EF
Operation criteria
Table 473: MFADPSDE Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Io signal Sel
1=Measured Io
2=Calculated Io
1=Measured Io
Selection for used
Io signal
Uo signal Sel
1=Measured Uo
2=Calculated Uo
1=Measured Uo
Selection for used
Uo signal
Peak counter limit
2...20
1
2
Peak counter limit
for restriking EF
Start delay time
30...60000
ms
1
30
Start delay time
Reset delay time
0...60000
ms
1
500
Reset delay time
Pol reversal
0=False
1=True
0=False
Rotate polarizing
quantity
4.2.8.8
Monitored data
Table 474: MFADPSDE Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start
time / operate
time
FAULT_DIR
Enum
0=unknown
1=forward
2=backward
3=both
Detected fault
direction
DIRECTION
Enum
0=unknown
1=forward
2=backward
3=both
Direction infor-
mation
Table continues on the next page
Protection functions
1MRS757644 H
500
620 series
Technical Manual