Parameter
Values (Range)
Unit
Step
Default
Description
Curve parameter C 0.02...2.00
1
2.00
Parameter C for
customer program-
mable curve
Curve parameter D 0.46...30.00
1
29.10
Parameter D for
customer program-
mable curve
Curve parameter E 0.0...1.0
1
1.0
Parameter E for
customer program-
mable curve
Table 390: EFHPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Minimum operate
time
20...60000
ms
1
20
Minimum operate
time for IDMT
curves
Reset delay time
0...60000
ms
1
20
Reset delay time
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used meas-
urement mode
Io signal Sel
1=Measured Io
2=Calculated Io
1=Measured Io
Selection for used
Io signal
EFIPTOC Group settings
Table 391: EFIPTOC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
1.00...40.00
xIn
0.01
1.00
Start value
Start value Mult
0.8...10.0
0.1
1.0
Multiplier for scal-
ing the start value
Operate delay time 20...200000
ms
10
20
Operate delay time
Table 392: EFIPTOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 393: EFIPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
Io signal Sel
1=Measured Io
2=Calculated Io
1=Measured Io
Selection for used
Io signal
Protection functions
1MRS757644 H
384
620 series
Technical Manual