![ABB Relion 620 Series Technical Manual Download Page 320](http://html.mh-extra.com/html/abb/relion-620-series/relion-620-series_technical-manual_2838045320.webp)
Parameter
Values (Range)
Unit
Step
Default
Description
Operating curve
type
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
15=IEC Def. Time
Selection of time
delay curve type
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward
Directional mode
Characteristic an-
gle
-179...180
deg
1
60
Characteristic an-
gle
Max forward angle 0...90
deg
1
80
Maximum phase
angle in forward di-
rection
Max reverse angle
0...90
deg
1
80
Maximum phase
angle in reverse di-
rection
Min forward angle
0...90
deg
1
80
Minimum phase an-
gle in forward di-
rection
Min reverse angle
0...90
deg
1
80
Minimum phase an-
gle in reverse direc-
tion
Table 305: DPH3LPDOC Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Type of reset curve 1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate
Selection of reset
curve type
Pol quantity
1=Self pol
4=Neg. seq. volt.
5=Cross pol
7=Pos. seq. volt.
5=Cross pol
Reference quantity
used to determine
fault direction
Protection functions
1MRS757644 H
320
620 series
Technical Manual