Figure 590: Drop-off period is longer than the set Reset delay time
When the drop-off period is longer than the set
Reset delay time, as described
, the input signal for the definite timer (here: timer input) is active,
provided that the current is above the set
Start value. The input signal is inactive
when the current is below the set
Start value and the set hysteresis region. The
timer input rises when a fault current is detected. The definite timer activates the
START
output and the operate timer starts elapsing. The reset (drop-off) timer
starts when the timer input falls, that is, the fault disappears. When the reset (drop-
off) timer elapses, the operate timer is reset. Since this happens before another
start occurs, the
OPERATE
output is not activated.