![ABB Relion 620 Series Technical Manual Download Page 539](http://html.mh-extra.com/html/abb/relion-620-series/relion-620-series_technical-manual_2838045539.webp)
Vector group of
the transformer
Winding 1 type Winding 2 type
Clock number
Zro A
Elimination
Dd6
D
d
Clk Num 6
Not needed
Dd8
D
d
Clk Num 8
Not needed
Dd10
D
d
Clk Num 10
Not needed
Dy1
D
y
Clk Num 1
Not needed
Dyn1
D
yn
Clk Num 1
Not needed
Dy5
D
y
Clk Num 5
Not needed
Dyn5
D
yn
Clk Num 5
Not needed
Dy7
D
y
Clk Num 7
Not needed
Dyn7
D
yn
Clk Num 7
Not needed
Dy11
D
y
Clk Num 11
Not needed
Dyn11
D
yn
Clk Num 11
Not needed
Yz1
Y
z
Clk Num 1
Not needed
YNz1
YN
z
Clk Num 1
Not needed
YNzn1
YN
zn
Clk Num 1
LV side
Yzn1
Y
zn
Clk Num 1
Not needed
Yz5
Y
z
Clk Num 5
Not needed
YNz5
YN
z
Clk Num 5
Not needed
YNzn5
YN
zn
Clk Num 5
LV side
Yzn5
Y
zn
Clk Num 5
Not needed
Yz7
Y
z
Clk Num 7
Not needed
YNz7
YN
z
Clk Num 7
Not needed
YNzn7
YN
zn
Clk Num 7
LV side
Yzn7
Y
zn
Clk Num 7
Not needed
Yz11
Y
z
Clk Num 11
Not needed
YNz11
YN
z
Clk Num 11
Not needed
YNzn11
YN
zn
Clk Num 11
LV side
Yzn11
Y
zn
Clk Num 11
Not needed
Zy1
Z
y
Clk Num 1
Not needed
Zyn1
Z
yn
Clk Num 1
Not needed
ZNyn1
ZN
yn
Clk Num 1
HV side
ZNy1
ZN
y
Clk Num 1
Not needed
Zy5
Z
y
Clk Num 5
Not needed
Zyn5
Z
yn
Clk Num 5
Not needed
ZNyn5
ZN
yn
Clk Num 5
HV side
ZNy5
ZN
y
Clk Num 5
Not needed
Zy7
Z
y
Clk Num 7
Not needed
Zyn7
Z
yn
Clk Num 7
Not needed
Table continues on the next page
1MRS757644 H
Protection functions
620 series
Technical Manual
539