4.7.1.6
Signals
Table 684: UEXPDIS Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
U_A_AB
SIGNAL
0
Phase-to-earth volt-
age A or phase-to-
phase voltage AB
U_B_BC
SIGNAL
0
Phase-to-earth volt-
age B or phase-to-
phase voltage BC
U_C_CA
SIGNAL
0
Phase-to-earth volt-
age C or phase-to-
phase voltage CA
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
EXT_LOS_DET
BOOLEAN
0=False
External signal for
excitation loss detec-
tion
Table 685: UEXPDIS Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
4.7.1.7
Settings
Table 686: UEXPDIS Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Diameter
1...6000
%Zn
1
200
Diameter of the
Mho diagram
Offset
-1000...1000
%Zn
1
-10
Offset of top of
the impedance cir-
cle from the R-axis
Displacement
-1000...1000
%Zn
1
0
Displacement of
impedance circle
centre from the X-
axis
Operate delay time 60...200000
ms
10
5000
Operate delay time
Protection functions
1MRS757644 H
726
620 series
Technical Manual