![ABB Relion 620 Series Technical Manual Download Page 942](http://html.mh-extra.com/html/abb/relion-620-series/relion-620-series_technical-manual_2838045942.webp)
Name
Type
Values (Range)
Unit
Description
U_RANGE_BC
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
U23 Amplitude
range
U_INST_CA
FLOAT32
0.00...4.00
xUn
U31 Amplitude,
magnitude of in-
stantaneous val-
ue
U_ANGL_CA
FLOAT32
-180.00...180.00
deg
U31 angle
U_DB_CA
FLOAT32
0.00...4.00
xUn
U31 Amplitude,
magnitude of re-
ported value
U_DMD_CA
FLOAT32
0.00...4.00
xUn
Demand value of
U31 voltage
U_RANGE_CA
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
U31 Amplitude
range
U_INST_A
FLOAT32
0.00...5.00
xUn
UL1 Amplitude,
magnitude of in-
stantaneous val-
ue
U_ANGL_A
FLOAT32
-180.00...180.00
deg
UL1 angle
U_DMD_A
FLOAT32
0.00...5.00
xUn
Demand value of
UL1 voltage
U_INST_B
FLOAT32
0.00...5.00
xUn
UL2 Amplitude,
magnitude of in-
stantaneous val-
ue
U_ANGL_B
FLOAT32
-180.00...180.00
deg
UL2 angle
U_DMD_B
FLOAT32
0.00...5.00
xUn
Demand value of
UL2 voltage
U_INST_C
FLOAT32
0.00...5.00
xUn
UL3 Amplitude,
magnitude of in-
stantaneous val-
ue
U_ANGL_C
FLOAT32
-180.00...180.00
deg
UL3 angle
U_DMD_C
FLOAT32
0.00...5.00
xUn
Demand value of
UL3 voltage
Measurement functions
1MRS757644 H