6.6.6
Signals
Table 874: MDSOPT Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0=False
Block input status
POS_ACTIVE
BOOLEAN
0=False
When active indicates the equip-
ment is running
RESET
BOOLEAN
0=False
Resets the accumulated operation
time to initial value
Table 875: MDSOPT Output signals
Name
Type
Description
ALARM
BOOLEAN
Alarm accumulated operation time
exceeds Alarm value
WARNING
BOOLEAN
Warning accumulated operation
time exceeds Warning value
6.6.7
Settings
Table 876: MDSOPT Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Warning value
0...299999
h
1
8000
Warning value for
operation time su-
pervision
Alarm value
0...299999
h
1
10000
Alarm value for op-
eration time super-
vision
Table 877: MDSOPT Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Initial value
0...299999
h
1
0
Initial value for op-
eration time super-
vision
Operating time
hour
0...23
h
1
0
Time of day when
alarm and warning
will occur
Operating time
mode
1=Immediate
2=Timed Warn
3=Timed Warn Alm
1=Immediate
Operating time
mode for warning
and alarm
1MRS757644 H
Supervision functions
620 series
Technical Manual
907