Table 914: RESCMMXU Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
A Hi high limit res
0.00...40.00
xIn
1
0.20
High alarm current
limit
A high limit res
0.00...40.00
xIn
1
0.05
High warning cur-
rent limit
A deadband res
100...100000
1
2500
Deadband configu-
ration value for in-
tegral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
Table 915: RESCMMXU Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Measurement
mode
1=RMS
2=DFT
2=DFT
Selects used meas-
urement mode
8.1.7.5
Monitored data
Table 916: RESCMMXU Monitored data
Name
Type
Values (Range)
Unit
Description
Io-A
FLOAT32
0.00...40.00
xIn
Measured residu-
al current
I_INST_RES
FLOAT32
0.00...40.00
xIn
Residual current
Amplitude, mag-
nitude of instan-
taneous value
I_ANGL_RES
FLOAT32
-180.00...180.00
deg
Residual current
angle
I_DB_RES
FLOAT32
0.00...40.00
xIn
Residual current
Amplitude, mag-
nitude of repor-
ted value
I_DMD_RES
FLOAT32
0.00...40.00
xIn
Demand value of
residual current
I_RANGE_RES
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
Residual current
Amplitude range
Max demand Io
FLOAT32
0.00...40.00
xIn
Maximum de-
mand for residu-
al current
Table continues on the next page
1MRS757644 H
Measurement functions
620 series
Technical Manual