![ABB Relion 620 Series Technical Manual Download Page 330](http://html.mh-extra.com/html/abb/relion-620-series/relion-620-series_technical-manual_2838045330.webp)
Here U represents the measured input voltage. The voltage slope characteristic is
graphically represented.
Figure 167: Effective start value or voltage slope characteristic
To achieve the voltage slope characteristics,
Voltage high limit must
always be set to a value greater than
Voltage low limit.
If
Voltage high limit is lower than Voltage low limit, the voltage step
characteristic is active with
Voltage low limit being the cutoff value.
The value of the setting
Start value should always be greater than the
setting
Start value low. Otherwise, Start value low is used as the effective
start value.
External input control mode
The External input control mode is used to enable voltage control from an external
application. If
Control mode is set to the "Input Control" mode, the effective start
value for all phases is influenced by the status of the binary input
ENA_U_MULT
.
If ENA
U
MULT isTRUE
Effective start value
Start value low
_
_
:
=
(Equation 9)
If ENA
U
MULT is FALSE
Effective start value
Start value
_
_
:
=
(Equation 10)
Protection functions
1MRS757644 H
330
620 series
Technical Manual