6.3
Advanced current circuit supervision for
transformers CTSRCTF
6.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Advanced current circuit supervision
for transformers
CTSRCTF
MCS 3I, I2
MCS 3I, I2
6.3.2
Function block
Figure 474: Function block
6.3.3
Functionality
The advanced current circuit supervision for transformers function CTSRCTF is
used for monitoring the current transformer secondary circuit where a separate
reference current transformer input for comparison is not available or where a
separate voltage channel for calculating or measuring the zero-sequence voltage
is not available. CTSRCTF can be used for detecting the single-phase failure on
the current transformer secondary for protection application involving two or three
sets of the three-phase current transformers.
CTSRCTF detects a fault in the measurement circuit and issues an alarm which can
be used for blocking the protection functions, for example, differential protection,
to avoid unwanted tripping.
CTSRCTF is internally blocked in case of a transformer under no-load condition or if
a current in any one phase exceeds the set maximum limit.
6.3.4
Operation principle
The function can be enabled and disabled with the
Operation setting. The
corresponding parameter values are "On" and "Off".
1MRS757644 H
Supervision functions
620 series
Technical Manual
885