Table 183: Station authority level “L,S,R” using R/L button
L/R Control
L/R Control status
Control access
R/L button
CTRL.LLN0.Loc
Sta
1
CTRL.LLN0.MltL
ev
L/R state
CTRL.LLN0.Loc
KeyHMI
Local user
IEC 61850 client
2
IEC 61850
client
3
Local
FALSE
FALSE
1
x
Remote
FALSE
FALSE
2
x
Remote
TRUE
FALSE
3
x
Off
FALSE
FALSE
0
Table 184: Station authority level “L,S,R” using CONTROL function block
L/R Control
L/R Control status
Control access
Control FB input
CTRL.LLN0.Lo
cSta
1
CTRL.LLN0.MltL
ev
L/R state
CTRL.LLN0.Loc
KeyHMI
Local user
IEC 61850 client
2
IEC 61850
client
3
CTRL_OFF
FALSE
FALSE
0
CTRL_LOC
FALSE
FALSE
1
x
CTRL_STA
TRUE
FALSE
3
x
CTRL_REM
4
TRUE
FALSE
3
x
CTRL_REM
FALSE
FALSE
2
x
CTRL_ALL
FALSE
FALSE
0
3.17.10.7
Station authority level “L,S,S+R,L+S,L+S+R”
Station authority level "L,S,S+R,L+S,L+S+R" adds station control access together
with several different multilevel access scenarios. Control access can also be
simultaneously permitted from local, station or remote location. Simultaneous local,
station or remote control operation is not allowed as one client and location at
time can access controllable objects and they remain reserved until the previously
started control operation is first completed by the client.
IED
IEC 61850
remote
IEC 61850
station
IEC 61850
remote
IEC 61850
remote
IEC 61850
remote
IED
IEC 61850
station
IED
IEC 61850
station
IED
IEC 61850
station
L+S
LOCAL
STATION
S+R
IEC 61850
remote
IEC 61850
remote
IED
IEC 61850
station
IED
IEC 61850
station
OFF
L+S+R
Figure 106: Station authority is “L,S,S+R,L+S,L+S+R”
When station authority level “L,S,S+R,L+S,L+S+R” is used, control access can be
selected using R/L button or CONTROL function block. IEC 61850 data object
1
Station client reserves the control operating by writing controllable point LocSta.
2
Client IEC 61850 command originator category is remote.
3
Client IEC 61850 command originator category is station.
4
CTRL_STA unconnected in application configuration. Station client reserves the control operat-
ing by writing controllable point LocSta
Basic functions
1MRS757644 H
186