Table 566: MNSPTOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Maximum operate
time
500000...7200000
ms
1000
1000000
Max operate time
regardless of the
inverse characteris-
tic
Minimum operate
time
100...120000
ms
1
100
Minimum operate
time for IDMT
curves
Cooling time
5...7200
s
1
50
Time required to
cool the machine
Table 567: MNSPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Current reference
0.30...2.00
xIn
0.01
1.00
Rated current (Ir) of
the machine (used
only in the IDMT)
Reset delay time
0...60000
ms
1
20
Reset delay time
4.4.4.9
Monitored data
Table 568: MNSPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time / op-
erate time
T_ENARESTART
INT32
0...10000
s
Estimated time to reset
of block restart
MNSPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.4.4.10
Technical data
Table 569: MNSPTOC Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: f
n
±1.5% of the set value or ±0.002 × I
n
Start time ,
I
Fault
= 2.0 × set
Start value
Minimum
Typical
Maximum
23
25 ms
28 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Table continues on the next page
1
Negative-sequence current before = 0.0, f
n
= 50 Hz, results based on statistical distribution of
1000 measurements.
2
Includes the delay of the signal output contact.
1MRS757644 H
Protection functions
620 series
Technical Manual