4.2.6.7
Settings
Table 454: HAEFPTOC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.05...5.00
xIn
0.01
0.10
Start value
Time multiplier
0.05...15.000
0.01
1.00
Time multiplier
in IEC/ANSI IDMT
curves
Operate delay time 100...200000
ms
10
600
Operate delay time
Operating curve
type
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
15=IEC Def. Time
Selection of time
delay curve type
Table 455: HAEFPTOC Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Minimum operate
time
100...200000
ms
10
500
Minimum operate
time for IDMT
curves
Type of reset curve 1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate
Selection of reset
curve type
Enable reference
use
0=False
1=True
0=False
Enable using cur-
rent reference from
other IEDs instead
of stand-alone
Table 456: HAEFPTOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Curve parameter A 0.0086...120.0000
1
28.2000
Parameter A for
customer program-
mable curve
Curve parameter B 0.0000...0.7120
1
0.1217
Parameter B for
customer program-
mable curve
Table continues on the next page
Protection functions
1MRS757644 H
466
620 series