Figure 408: Inverse-time characteristic curves for overload stage
If the integrated current exceeds 1.1 times the setting
Start value overload for
a short period but does not operate as the current decreases within
Start value
overload, the output
ST_OVLOD
is kept active but the operation timer is frozen.
However, if the integrated current exceeds 1.1 times the
Start value overload
setting value again, the operation timer continue from the freezing point. Thus,
the operation timer is cumulative. If the integrated current exceeds 1.1 times the
setting
Start value overload only once and remains within the Start value overload
area for 24 hours, the operation timer and the output
ST_OVLOD
are reset.