9.5.8
Monitored data
Table 1028: OLATCC Monitored data
Name
Type
Values (Range)
Unit
Description
TR0_I_AMPL
FLOAT32
0.00...15000.00
A
Transmitted cur-
rent magnitude
TR0_I_ANGL
FLOAT32
-180.00...180.00
deg
Transmitted cur-
rent angle
U_MEAS
FLOAT32
0.00...5.00
xUn
Phase-to-phase
voltage, average
filtered
ANGL_UA_IA
FLOAT32
-180...180
deg
Measured angle
value between
phase A voltage
and current
TIMER_STS
Enum
0=Timer off
1=Lower timer1
on
2=Raise timer1
on
3=Lower timer2
on
4=Raise timer2
on
5=Fast lower T
on
Timer T1, T2 or
fast lower timer
active
OPR_MODE_STS Enum
0=Not in use
1=Manual
2=Auto single
3=Auto master
4=Auto follower
5=MCC
6=NRP
The acting op-
eration mode
of the function
block
U_CTL
FLOAT32
0.000...3.000
xUn
Control voltage,
Up, target volt-
age level
UD_CTL
FLOAT32
-2.000...2.000
xUn
Voltage differ-
ence between
Measured volt-
age - Control
Voltage: Um - Up
Table continues on the next page
Control functions
1MRS757644 H
1078
620 series