Table 20: IEC 61850-8-1 MMS settings
Parameter
Values (Range)
Unit
Step
Default
Description
Unit mode
1=Primary
1
0=Nominal
2
2=Primary-Nominal
3
0=Nominal
IEC 61850-8-1 unit
mode
1
MMS client expects primary values from event reporting and data attribute reads.
2
MMS client expects nominal values from event reporting and data attribute reads; this is the
default for PCM600.
3
For PCM600 use only, When
Unit mode is set to "Primary", the PCM600 client can force its
session to "Nominal" by selecting "Primary-Nominal" and thus parameterizing in native form. The
selection is not stored and is therefore effective only for one session. This value has no effect if
selected via the LHMI.
1MRS757644 H
Basic functions
620 series
Technical Manual