![ABB Relion 620 Series Technical Manual Download Page 203](http://html.mh-extra.com/html/abb/relion-620-series/relion-620-series_technical-manual_2838045203.webp)
Parameter
Values (Range)
Unit
Step
Default
Description
Description
SPCLGAPC1 Output
15
Generic control point description
Operation mode
0=Pulsed
1=Toggle/Persistent
-1=Off
-1=Off
Operation mode for generic con-
trol point
Pulse length
10...3600000
ms
10
1000
Pulse length for pulsed operation
mode
Description
SPCLGAPC1 Output
16
Generic control point description
3.17.14
Programmable buttons FKEYGGIO
3.17.14.1
Function block
Figure 111: Function block
3.17.14.2
Functionality
The programmable buttons function FKEYGGIO is a simple interface between the
panel and the application. The user input from the buttons available on the front
panel is transferred to the assigned functionality and the corresponding LED is ON
or OFF for indication. The behavior of each function key in the specific application is
configured by connection with other application functions. This gives the maximum
flexibility.
3.17.14.3
Operation principle
Inputs
L1..L16
represent the LEDs on the protection relay's LHMI. When an input is
set to TRUE, the corresponding LED is lit. When a function key on LHMI is pressed,
the corresponding output
K1..K16
is set to TRUE.
1MRS757644 H
Basic functions
620 series
Technical Manual
203