14.6
RTD/mA inputs
Table 1090: RTD/mA inputs
Description
Value
RTD inputs
Supported RTD sensors
100 Ω platinum
250 Ω platinum
100 Ω nickel
120 Ω nickel
250 Ω nickel
10 Ω copper
TCR 0.00385 (DIN 43760)
TCR 0.00385
TCR 0.00618 (DIN 43760)
TCR 0.00618
TCR 0.00618
TCR 0.00427
Supported resistance range
0...2 kΩ
Maximum lead resistance
(three-wire measurement)
25 Ω per lead
Isolation
2 kV (inputs to protective earth)
Response time
<4 s
RTD/resistance sensing cur-
rent
Maximum 0.33 mA rms
Operation accuracy
Resistance
Temperature
± 2.0% or ±1 Ω
±1°C
10 Ω copper: ±2°C
mA inputs
Supported current range
0…20 mA
Current input impedance
44 Ω ± 0.1%
Operation accuracy
±0.5% or ±0.01 mA
1MRS757644 H
Technical data
620 series
Technical Manual