Note
Action
Tap to select the mechanical unit and then tap
Calib. Parameters
.
en0400001127
3
Tap
Fine Calibration...
.
4
A dialog box is displayed, urging you to use ex-
ternal equipment to perform the actual calibration.
Make sure all necessary calibration equipment is
fitted for the axis to be calibrated.
A dialog box is displayed, warning that updating
the revolution counters may change programmed
robot positions:
•
Tap
Yes
to proceed.
•
Tap
No
to cancel.
Select the check-box for the current axis/axes to
be calibrated.
5
Tap
Calibrate
.
6
A dialog box is displayed, warning that calibration
of the selected axes will be changed, which cannot
be undone:
•
Tap
Calibrate
to proceed.
•
Tap
Cancel
to cancel.
Tapping
Calibrate
results in briefly displaying a
dialog box, announcing that the calibration pro-
cess has started.
The axis is calibrated and the system returns to
the list of available mechanical units.
Checking and finalizing the calibration
Note
Action
Release the brakes and manually rotate the axis
to apart the calibration pins from each other. This
is done to avoid damage on the pins if incorrect
operation should occur during next step of jog-
ging.
1
Continues on next page
852
Product manual - IRB 1200
3HAC046983-001 Revision: S
© Copyright 2014 - 2021 ABB. All rights reserved.
5 Calibration
5.6.5 Manual calibration method - calibrating axis 3
Continued