5.6.4 Manual calibration method - calibrating axis 2
Calibration position of axis 2
The figure shows axis 2 in calibration position.
xx1400001201
Required equipment
Calibration of axis 2 is done by moving the lower arm so that the calibration pin
and calibration stop touches each other gently.
These parts are already fitted to the robot, no extra installation of calibration
equipment is required.
See figures below for reference, and follow the step-by-step procedure that follows.
Calibration stop
Calibration pin
xx1400001136
xx1400001135
The axis-2 mechanical stop fitted to the
swing is used for calibration of axis 2.
The press fit mechanical stop pin fitted to the
lower arm is used for calibration of axis 2.
No additional equipment is required.
No additional equipment is required.
Continues on next page
Product manual - IRB 1200
845
3HAC046983-001 Revision: S
© Copyright 2014 - 2021 ABB. All rights reserved.
5 Calibration
5.6.4 Manual calibration method - calibrating axis 2