A parameter is designated as follows:
Pr0.00
No.
Class
・
For
“ Attribute ”,refer to P.3-38
“ Details of Attribute ”.
・
P.2-47
〜
“
Wiring to the Connector
,
X4
”
Default: [ ]
Rev.2.00
1
Before Using the Products
2
Preparation
3
Setup
4
Trial Run
5
Adjustment
6
When In T
roubie
7
Supplement
4. Details of Parameter
[Class 4] I/F Monitor Setting
Pr4.57
Position comparison output
assignment setting
Range
Unit
Attribute
Default
Related
control code
-2147483648 to
2147483647
—
R
0
P S T
Sets output terminal corresponding to position compare 1 to 8 by bit.
Multiple position comparison values can be set by one single output terminal.
・
Set bits
bit
Designation
bit0 to bit3
Position com 1
bit4 to bit7
Position com 2
bit8 to bit11
Position com 3
bit12 to bit15
Position com 4
bit16 to bit19
Position com 5
bit20 to bit23
Position com 6
bit24 to bit27
Position com 7
bit28 to bit31
Position com 8
・
Set value for each bit
*1 *2
Setup value
Designation
0000b
Invalid output
0001b
Assigned to SO1 or OCMP1
0010b
Assigned to SO2 or OCMP2
0011b
Assigned to SO3 or OCMP3
Others
For manufacturer’s use (do not set)
*1 When general output (SO1 to SO3) is used as position comparision output(CMP-OUT),assign position
comparision to Pr4.10 to Pr4.12 for all control modes.
*2 When encoder output signal(OA,OB) is used as position comparision output(OCMP1 to 3),set Pr4.47 to 1.