As protection of an alarm requiring emergency stop occurs,please set an allowable over-speed
level for Pr6.15 “2nd over-speed level setup”.
For the immediate cessation of an error corresponding to the second overspeed protection trip
and the error is generated.but, set Pr5.13 to a small value with a sufficient margin for Pr6.15.
If the margin is insufficient or the set value is the same, both Err26.0 and Err26.1 may be
detected. In this case, Err26.0 will be displayed. However, because Err26.1 is also activated
internally, priority is given to the alarm that does not require emergency stop, and emergency
stop is not executed.
・
When there is a plurality of alarm, LED front panel will display the information previously generated.
When confirmed by USB communication (PANATERM)
・
Ararm Screen …Plurality of content for An error occurred in the current is displayed.
(
First, the first line
)
・
Other Screen…… Only the previously generated content is displayed
.
1.When in Trouble
Emergency
Stop upon Occurrence of Alarm
Caution