Mounting Direction and Spacing
• Reserve enough surrounding space for effective cooling.
• Install fans to provide uniform distribution of temperature in the control panel.
• D to F-frame is provided with a cooling fan at the bottom.
•
Observe the environmental conditions of the control panel described in the previous page.
• Check that the ambient temperature of 50 mm around the servo amplifier does not
exceed the operating temperature range.
•
If the temperature can not be measured beyond a distance of 50 mm, please measure
at the midpoint between the obstacle and the servo amplifier .
Note
It is recommended to use the conductive paint when you make your own mounting brack
-
et, or repaint after peeling off the paint on the machine for installing the products, in order
to make noise countermeasure.
Caution on Installation
Caution
• In case the product malfunctions due to external noise disturbance and static electricity (signal
disconnection, signal phase loss etc.), it will result in unexpected action very likely. It is highly
recommended that you make a fail-safe design and secure the safety in the operative range.
• If stranded wires are used as the cable, bunch the conductors of the cable using a rod terminals
or a round terminals. If stranded wires are used as they are, unexpected accidents such as an
electric shock and short circuit or injury may result.
• Be sure to install a circurt breaker (MCCB) in the power supply. In addition, be sure to ground
the grounding terminal or grounding wire provided. (In order to prevent electric shock and mal
-
functions, Class D grounding [grounding resistance of 100 Ω or less] is recommended.)
If the product is grounded insufficiently, not only the driver may not deliver its performance suf
-
ficiently, but also safety hazards such as a malfunction due to a electrification or a disturbance
may be caused.
• If electric wires are bound and run through metal duct, they cannot carry the rated current due to
temperature rise. If they are forced to carry the rated current, they may burn. When determining
size of the wire.
• Do not use or store the product in a place subject above to 5.88 m/s
2
or more vibration or shock,
foreign materials such as dust, metallic powder and oilmist, liquids such as water, oil and grind-
ing fluid, close to flammable materials, or in an atmosphere of corrosive gas (H
2
S, SO
2
, NO
2
, Cl
2
,
etc.) or inflammable gas under any circumstance.
a
a
a
Fan
Fan 100 mm
or more
100 mm
or more
40 mm
or
more
40 mm
or
more
Direction of air flowing
from the internal
cooling fan (D to F-frame)
Control panel
4. Installation
Driver
a
A to F-frame
10 mm or more
Related page
• P.1-8 “Specifications” • P.2-25 “Installation Motor”
• P.7-32 “Dimensions D
river
” • P.7-101 “Mounting Bracket”