6. Application Functions
Deterioration Diagnosis Warning Function
・
The upper limit and lower limit values for torque command average can be set by
parameters Pr5.77 and 5.78 respectively. Deterioration diagnostic warning number AC is
generated in case these upper or lower limit values have been exceeded for changes in
the load characteristic estimates.
i) Legond for torque command average deterioration diagnosis warning not cccured.
ii) Legond for torque command average deterioration diagnosis warning cccured.
Pr5.77(upper limit)
Torque command
velocity
Pr5.75
+Pr4.35
-
Pr4.35
Torque command
average deterioration
diagnosis valid section
Pr5.76
(Deterioration diagnosis
torque average time)
Deterioration
diagnosis velocity
output V-DIAG
Torque command average
Pr5.78(lower limit)
Deterioration
diagnosis velocity
output V-DIAG
velocity
Pr5.76
(Deterioration diagnosis
torque average time)
Torque command average
Torque command
average deterioration
diagnosis valid section
Pr5.77(upper limit)
Pr5.78(lower limit)
Torque command
Pr5.75
+Pr4.35
-
Pr4.35
Deterioration diagnosis
warning
WngACh
When torque command average
deterioration diagnosis valid section,
warning is generated in case Pr5.77
(
upper limit
)
/ Pr5.78
(
lower limiter
)
values have been exceeded.