Pr7.95
Number of RTEX continuous
communication error protection 1 detections
Range
Unit
Attribute
Default
Related
control code
0 to 17
times
R
4
P S T
Set the number of RTEX continuous communication error protection 1 detections.
If a continuous CRC error occurs exceeding the number of times set for this parameter,
Err83.0 “RTEX continuous communication error protection 1” occurs.
If 0 or 1 is set for this parameter, 2 is internally set.
Pr7.96
Number of RTEX continuous
communication error protection 2 detections
Range
Unit
Attribute
Default
Related
control code
0 to 17
times
R
12
P S T
Set the number of RTEX continuous communication error protection 2 detections.
If an interrupt omission, CRC error, MAC-ID error, C/R error or cyclic data error occurs
exceeding the number of times set for this parameter, Err83.1 “RTEX continuous
communication error protection 2” occurs.
If 0 or 1 is set for this parameter, 2 is internally set.
Pr7.97
Number of RTEX communication
timeout error protection detections
Range
Unit
Attribute
Default
Related
control code
0 to 17
times
R
4
P S T
Set the number of times for RTEX communication timeout error protection detection.
If 0 or 1 is set for this parameter, 2 is internally set.
Pr7.98
Number of RTEX cyclic data error
protection 1/2 detections
Range
Unit
Attribute
Default
Related
control code
0 to 17
times
R
4
P S T
Set the number of times for RTEX cyclic data error protection 1/2 detection.
If a continuous cyclic error occurs exceeding the number of times set for this parameter,
Err86.0 or Err86.1 “RTEX cyclic data error protection 1 or 2” occurs.
If 0 or 1 is set for this parameter, 2 is internally set.
Pr7.99
RTEX function extended setup 6
Range
Unit
Attribute
Default
Related
control code
-32768 to 32767
-
B
0
P S T
Content
setup value
bit0
Activation of operation command (trial run, FFT, etc.)
execution by USB communication (PANATERM) when
TEX communication established.
0
Invalid
1
Valid
bit1 to 2
For manufacturer’s use
bit3
Command pulse aggregate value [command units]
output setting.
0
Before filter
1
After filter
bit4 to 6
For manufacturer’s use
bit7
RTEX monitor command regenerative load factor unit
switching
0
[%]
1
[0.1%]
bit8 to 15
For manufacturer’s use
4. Details of Parameter