• C to D-frame (100 V/200 V Type)
Name
Symbol
Description
Connector
Pin No.
Connetor
XA
Main power
input terminal
L1
5
100 V type
:
Single phase AC100 to 120
V
+10 %
−15 %
50/60 Hz input.
200 V type
:
Single phase/3-phase
AC200 to 240
V
+10 %
−15 %
50/60 Hz input.
Use L1 and L3 terminal for single phase input.
L2
4
L3
3
Control power
input terminal
L1C
2
100 V type
:
Single phase AC100 to 120
V
+10 %
−15 %
50/60 Hz input.
200 V type
:
Single phase AC200 to 240
V
+10 %
−15 %
50/60 Hz input.
L2C
1
XB
Regen resistor
connecting
terminal
P
6
Normally, short out the circuit between B and RB.
When a trip happens due to a regenerative load protection error, open the circuit
between B and RB and connect an external regenerative resistor (prepared by
customer) between P and B. Then, specify the external regenerative resistor for
the parameter Pr0. 16 set to 1 or 2.
RB
5
B
4
Motor
connecting
terminal
U
3
Connect each phase of the motor winding.
U: U phase V: V phase W: W phase
V
2
W
1
Earth terminal
Earth terminal for grounding. Two terminals are arranged, one of them connect to
the ground, and the other is connected with the earth line of the motor.
System Configuration and Wiring
When the alarm is generated, the main power supply has to be turned off.
Noise filter
MC
MCCB
L
Main power
supply
Control power
supply
37
ALM+
L2
L3
L1C
L2C
P
ALM
OFF
RB
B
U
V
W
L1
Coil surge suppression units
ALM−
Motor
connection
XA
XB
X4
36
ON
MC
ALM
Built-in thermal
protector of an
external
regenerative
resistor
(light yellow)
External regenerative resistor
Note.1) Short wire
Note.1) Short wire
• In Case of Leadwire type
Main power
supply
Control power
supply
37
ALM+
L2
L3
L1C
L2C
P
ALM
OFF
RB
B
U
V
W
L1
Coil surge suppression units
ALM−
Motor
connection
XA
XB
X4
36
ON
MC
ALM
Built-in thermal
protector of an
external
regenerative
resistor
(light yellow)
External regenerative resistor
• In Case of connector type
Insulated
DC12 to 24 V
(±5 %)
+
−
Insulated
DC12 to 24 V
(±5 %)
+
−
For manu-
facturer’s use
N
P
XC
Do not connect anything.
For manu-
facturer’s use
N
P
XC
Do not connect anything.
Noise filter
MC
MCCB
L
For single phase
wiring, L2 is not
used.
For single phase
wiring, L2 is not
used.
172159-1
172167-1
Red
White
Black
Green
M
1
2
3
4
1
2
3
4
M
The regenerative resistor is built into C, D-frame.
The external regenerative resistor can be built to C, D-frame.
5.
Wiring of the Main Circuit
C to D-frame (100 V/200 V Type)
Note
Note
Related page
The wiring indicated with the broken line shall be provided only when required.
• P.2-40 “Specifications of Motor Connector” • P.2-39 “Wiring Method to Driver Connector”