Digital Operator Display Functions and Levels
5-
7
H4-02
Gain
(termi-
nal
FM)
Set
the voltage level gain for multi-
function
analog output 1.
Set
the number of multiples of 10 V to
be
output as the 100% output for the
monitor
items. Voltage output from
the
terminals, however, is 10 V max.
A
meter calibration function is avail-
able.
0.00
to
2.50
1.00
Yes
Q
Q
Q
41EH
Terminal
FM
Gain
H4-05
Gain
(termi-
nal
AM)
Set
the voltage level gain for multi-
function
analog output 2.
Set
the number of multiples of 10 V to
be
output as the 100% output for the
monitor
items. Voltage output from
the
terminals, however, is 10 V max.
A
meter calibration function is avail-
able.
0.00
to
2.50
0.50
Yes
Q
Q
Q
421H
Terminal
AM
Gain
L1-01
Motor
pro-
tection
selection
Set
to enable or disable the motor
overload
protection function using the
electronic
thermal relay.
0:
Disabled
1:
General-purpose motor protection
2:
Inverter motor protection
3:
Vector motor protection
In
some applications when the
Inverter
power supply is turned off,
the
thermal value is reset, so even if
this
parameter is set to 1, protection
may
not be effective.
When
several motors are connected to
one
Inverter, set to 0 and ensure that
each
motor is installed with a protec-
tion
device.
0
to 3
1
No
Q
Q
Q
480H
MOL
Fault
Select
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Regis-
ter
LCD
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor