Wiring Control Circuit Terminals for Asian Models
2-
35
The
functions of DIP switch S1 are shown in the following table.
n
Sinking/Sourcing
Mode
The
input terminal logic can be switched between sinking mode (0-V common) and sourcing mode (+24-V
common)
if shunt connector CN5 is used. An external 24-V power supply is also supported, providing more
freedom
in signal input methods.
Table 2.17 DIP Switch S1
Name
Function
Setting
S1-1
RS-485
and RS-422A terminating resis-
tance
OFF:
No terminating resistance
ON:
Terminating resistance of 110
Ω
S1-2
Input
method for analog input A2
OFF:
0 to 10 V (internal resistance: 20 k
Ω
)
ON:
4 to 20 mA (internal resistance: 250
Ω
)
Table 2.18 Sinking/Sourcing Mode and Input Signals
Internal
Power
Supply
External
Power
Supply
Sink-
ing
Mode
Sourc-
ing
Mode
IP24V (24 V)
CN5 (NPN set) Factory setting
SC
S1
S2
CN5
Shunt
position
IP24V (24 V)
CN5 (EXT set)
SC
S1
S2
Ex24 V
CN5
IP24V (24 V)
CN5 (PNP set)
SC
S1
S2
CN5
IP24V (24 V)
CN5 (EXT set)
SC
S1
S2
Ex 24 V
CN5
Содержание SYSDRIVE 3G3RV
Страница 1: ...USER S MANUAL SYSDRIVE 3G3RV High function General purpose Inverters Cat No I532 E1 1...
Страница 36: ...1 22...
Страница 106: ...3 14...
Страница 126: ...4 20...
Страница 216: ...5 90...
Страница 388: ...7 26...