5
-26
* 1. The
factory setting depends on the capacity of the Inverter.
* 2. The
setting range depends on the capacity of the Inverter.
* 3. This
parameter can be monitored or set only when 1 is set for C6-01 and F is set for C6-02.
C6-03
Carrier
frequency
upper
limit
Set
the carrier frequency upper
limit
and lower limit in kHz units.
The
carrier frequency gain is set as
follows:
With
the vector control method, the
upper
limit of the carrier frequency
is
fixed in C6-03.
K
is a coefficient that depends on the
setting
of C6-03.
C6-03
≥
10.0 kHz: K = 3
10.0
kHz > C6-03
≥
5.0 kHz: K = 2
5.0
kHz > C6-03: K = 1
2.0 to
15.0
*2
*3
15.0
kHz
*1
No
A
A
A
225H
6-2
Carrier-
Freq
Max
C6-04
Carrier
frequency
lower
limit
0.4 to
15.0
*2
*3
15.0
kHz
*1
No
A
A
No
226H
6-2
Carrier-
Freq
Min
C6-05
Carrier
frequency
propor-
tional
gain
00
to
99
*3
00
No
A
A
No
227H
6-2
Carrier-
Freq
Gain
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register
Page
LCD
Display
V/f
V/f
with
PG
Open
Loop
Carrier frequency
Output frequency x (C6-05) x K
(Max. output frequency)
Output
frequency