Specifications of Options and Peripheral Devices
9-
5
Specifications
of
Options
and
Peripheral
Devices
The
following options and peripheral devices can be used for the Inverter. Select them according to the
application.
* Use
a ground fault interrupter with a current sensitivity of 200 mA minimum and an operating time of 0.1 s minimum to prevent
operating
errors. The interrupter must be suitable for high-frequency operation.
Example:NV
series by Mitsubishi Electric Corporation (manufactured in or after 1988)
EG,
SG series by Fuji Electric Co., Ltd. (manufactured in or after 1984)
Table 9.4 Options and Peripheral Devices
Purpose
Name
Model
(Code)
Description
Protect
Inverter wiring
MCCB
or Ground
Fault
Interrupter
*
Example:
Mitsubishi
Electric’s
NV Series
Always
connect a breaker to the power supply line to pro-
tect
Inverter wiring. Use a ground fault interrupter suitable
for
high frequencies.
Prevents
burning when
a
Braking Resistor is
used.
Magnetic
Contac-
tor
Example:
Fuji Electric’s
SC
Series
Install
to prevent the braking resistor from burning out
when
one is used. Always attach a surge absorber to the
coil.
Contains
switching
surge
Surge
Absorber
DCR2-
o
Absorbs
surge from the magnetic contactor and control
relays.
Connect surge absorbers to all magnetic contactors
and
relays near the Inverter.
Isolates
I/O signals
Isolator
DGP
o
Isolates
the I/O signals of the Inverter and is effective
against
inductive noise.
Improve
the input
power
factor of the
Inverter
DC
Reactor
AC
Reactor
3G3HV-PUZDAB
o
3G3IV-PUZBAB
o
Used
to improve the input power factor of the Inverter. All
Inverters
of 22 kW or higher contain built-in DC reactors.
These
are optional for Inverters of 18.5 kW or less. Install
DC
and AC reactors for applications with a large power
supply
capacity (600 kVA or higher).
Reduce
the affects of
radio
and control device
noise
Input
Noise Filter
3G3IV-PFN
o
3G3EV-PLNF
o
Reduces
noise coming into the inverter from the power
supply
line and to reduce noise flowing from the inverter
into
the power supply line. Connect as close to the
Inverter
as possible.
Output
Noise Fil-
ter
3G3IV-PLF
o
Reduces
noise generated by the Inverter. Connect as close
to
the Inverter as possible.
Enable
stopping the
machine
in a set time
Braking
Resistor
3G3IV-PERF150WJ
o
01
Consumes
the regenerative motor energy with a resistor to
reduce
deceleration time (use rate: 3% ED).
Braking
Resistor
Unit
3G3IV-PLKEB
o
Consumes
the regenerative motor energy with a resistor to
reduce
deceleration time (use rate: 10% ED).
Braking
Unit
3G3IV-PCDBR
o
B
Used
with a Braking Resistor Unit to reduce the decelera-
tion
time of the motor.
Operates
the Inverter
externally
Analog
Operator
(small
plastic
Operator)
3G3IV-PJVOP95
o
Allows
frequency reference settings and ON/OFF opera-
tion
control to be performed by analog references from a
remote
location (50 m max.).
Frequency
counter specifications: 60/120 Hz, 90/180Hz
Analog
Operator
(Standard
steel-
plate
Operator)
3G3IV-PJVOP96
o
Allows
frequency reference settings and ON/OFF opera-
tion
control to be performed by analog references from a
remote
location (50 m max.).
Frequency
counter specifications: 75 Hz, 150 Hz, 220 Hz
Digital
Operator
Connection
Cable
1
m cable: (3G3IV-
PCN126)
3
m cable: (3G3IV-
PCN326)
Extension
cable to use a Digital Operator remotely.
Cable
length: 1 m or 3 m
Provides
Inverter
momentary
power loss
recovery
time
Momentary
Power
Loss
Recovery
Unit
3G3IV-PCN
o
26
Handles
momentary power losses for the control power
supply
for models 2.2 kW or less (maintains power for
2 s).
Set/monitor
frequen-
cies
and voltages exter-
nally.
Scaling
Meter
K3TJ-V11
o
Measures
the output voltage externally and designed for
use
with a PWM Inverter.
Power supply
MCCB or
ground fault
interrupter
Magnetic
contactor
AC Reactor to
improve power
factor
Braking
Resistor
Inverter
Input-line
noise filter
DC
Reactor
Ground
Ground
Output-line
noise filter
Motor
Analog
Operator