Parameter Tables
5-
61
n
Reference
Detection:
L4
Parameters
for the reference detection function are shown in the following table.
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register Page
LCD
Display
V/f
V/f
with
PG
Open
Loop
L4-01
Speed
agreement
detection
level
Effective
when “Desired fre-
quency
(ref/setting) agree
1,”
“Frequency detection 1,”
or
“Frequency detection 2”
is
set for a multi-function
output.
Frequencies
to be detected
are
set in Hz units.
0.0
to
400.0
0.0
Hz
No
A
A
A
499H
-
Spd
Agree
Level
L4-02
Speed
agreement
detection
width
Effective
when “Frequency
(speed)
agree 1,” “Desired
frequency
(speed) agree 1,”
or
“Frequency (FOUT)
detection
1,” is set for a
multi-function
output.
Sets
the frequency detection
width
in Hz units.
0.0
to
20.0
2.0
Hz
No
A
A
A
49AH
-
Spd
Agree
Width
L4-03
Speed
agreement
detection
level
(+/-)
Effective
when “Desired fre-
quency
(speed) agree 2,”
“Desired
frequency (speed)
agree
1” “Frequency
(FOUT)
detection 3,” or
“Frequency
(FOUT) detec-
tion
4” is set for a multi-
function
output.
Frequency
detection width is
set
in Hz units.
-400.0
to
+400.0
0.0
Hz
No
A
A
A
49BH
-
Spd
Agree
Lvl+-
L4-04
Speed
agreement
detection
width
(+/-)
Effective
when “Frequency
(speed)
agree 2,” “Desired
frequency
(speed) agree 1,”
or
“Frequency detection 4"
is
set for a multi-function
output.
Frequency
detection width is
set
in Hz units.
0.0
to
20.0
2.0
Hz
No
A
A
A
49CH
-
Spd
Agree
Width+-
L4-05
Operation
when
fre-
quency
ref-
erence
is
lost
0: Stop
(Operation follows
the
frequency reference.)
1: Continue
speed opera-
tion
according to setting
of
L4-06. (At 80% of
speed
before the fre-
quency
reference was
lost)
Frequency
reference is lost:
Frequency
reference
dropped
over 90% in 400
ms.
0
or 1
0
No
A
A
A
49DH
6-58
Ref
Loss
Sel
L4-06
Frequency
reference
for
loss of
frequency
reference
Enables
operation selection
when
frequency reference is
lost
and operation at the fol-
lowing
speed:
(Speed
prior to loss) x L4-06
0.0
to
100.0%
80.0
No
A
*
A
*
A
*
4C2H
-
Fref
at Floss
*
For (-E) models only. Otherwise always 80.0%.