3
-10
n
Setting
Parameters
Here,
the procedure is shown to change C1-01 (Acceleration Time 1) from 10 s to 20 s.
Table 3.3 Setting Parameters in Advanced Programming Mode
Step
No.
Digital Operator Display
Description
1
Power
supply turned ON.
2
MENU
Key pressed to enter Drive Mode.
3
MENU
Key pressed to enter Quick Program-
ming
Mode.
4
MENU
Key pressed to Enter Advanced Pro-
gramming
Mode.
5
ENTER
pressed to access monitor display.
6
Increment
or Decrement Key pressed to dis-
play
C1-01 (Acceleration Time 1).
7
ENTER
Key pressed to access setting display.
The
setting of C1-01 (10.00) is displayed.
8
Digit
Selection/RESET Key pressed to move
the
flashing digit to the right.
9
Increment
Key pressed to change set value to
20.00
s.
10
ENTER
Key pressed to enter the set data.
“END”
is displayed for 10 s and then the
entered
value is displayed for 0.5 s.
11
The
monitor display for C1-01 returns.