5
-16
b5-10
PID
output
gain
Sets
output gain.
0.0
to
25.0
1.0
No
A
A
A
1AEH
6-118
Output
Gain
b5-11
PID
reverse
output
selection
0:
0 limit when PID output
is
negative.
1:
Reverses when PID
output
is negative.
0
limit when reverse prohibit
is
selected using b1-04.
0
or 1
0
No
A
A
A
1AFH
6-118
Output
Rev
Sel
b5-12
Selection
of
PID
feed-
back
com-
mand
loss
detection
0:
No detection of loss of
PID
feedback.
1:
Detection of loss of PID
feedback.
Operation
continues
during
detection, with the
malfunctioning
contact
not
operating.
2:
Detection of loss of PID
feedback.
Coasts
to stop during
detection,
and fault
contact
operates.
0
to 2
0
No
A
A
A
1B0H
6-118
Fb
los Det
Sel
b5-13
PID
feed-
back
com-
mand
loss
detection
level
Sets
the PID feedback loss
detection
level as a percent
units,
with the maximum
output
frequency at 100%.
0
to
100
0%
No
A
A
A
1B1H
6-118
Fb
los Det
Lvl
b5-14
PID
feed-
back
com-
mand
loss
detection
time
Sets
the PID feedback loss
detection
level in seconds.
0.0
to
25.5
1.0
s
No
A
A
A
1B2H
6-118
Fb
los Det
Time
b5-15
PID
sleep
function
operation
level
Set
the PID sleep function
start
level as a frequency.
Always
enabled for (-E)
models.
On other models, it
is
disabled when the PID
control
is not selected
(b5-01=0).
0.0
to
400.0
0.0
Hz
No
A
A
A
1B3H
6-118
PID
Sleep
Level
b5-16
PID
sleep
operation
delay
time
Set
the delay time until the
PID
sleep function starts in
seconds.
0.0
to
25.5
0.0
s
No
A
A
A
1B4H
6-119
PID
Sleep
Time
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Register Page
LCD
Display
V/f
V/f
with
PG
Open
Loop