Parameter Tables
5-
51
H3-09
Settings
Set-
ting
Value
Function
Contents (100%)
Control Methods
+1/
V/f
V/f
with
PG
Open
Loop
Vec-
tor
0
Add
to terminal A1
Maximum
output frequency
Yes
Yes
Yes
6-28
1
Frequency
gain
Frequency
reference (voltage) command
value
Yes
Yes
Yes
6-28
2
Auxiliary
frequency reference (2nd
step
analog)
Maximum
output frequency
Yes
Yes
Yes
6-28
4
Voltage
bias
Motor
rated voltage (E1-05)
Yes
Yes
No
-
5
Accel/decel
change (reduction
coefficient)
Set
acceleration and deceleration times (C1-
01
to C1-08)
Yes
Yes
Yes
6-21
6
DC
injection braking current
Inverter
rated output current
Yes
Yes
Yes
6-18
7
Overtorque/undertorque
detection
level
Motor
rated torque for vector control
Inverter
rated output current for V/f control
Yes
Yes
Yes
6-46
8
Stall
prevention level during run
Inverter
rated output current
Yes
Yes
No
6-43
9
Frequency
reference lower limit
level
Maximum
output frequency
Yes
Yes
Yes
6-33
A
Jump
frequency
Maximum
output frequency
Yes
Yes
Yes
6-30
B
PID
feedback
Maximum
output frequency
Yes
Yes
Yes
6-
120
C
PID
target value
Maximum
output frequency
Yes
Yes
Yes
6-
120
E
Motor
temperature input
10
V = 100%
Yes
Yes
Yes
6-51
10
Positive
torque limit
Motor's
rated torque
No
No
Yes
6-40
11
Negative
torque limit
Motor's
rated torque
No
No
Yes
6-40
12
Regenerative
torque limit
Motor's
rated torque
No
No
Yes
6-40
15
Positive/negative
torque limit
Motor's
rated torque
No
No
Yes
6-40
1F
Analog
input not used.
-
Yes
Yes
Yes
13,
14,
16
to 1F
Not
used
-
-
-
-
-
Содержание SYSDRIVE 3G3RV
Страница 1: ...USER S MANUAL SYSDRIVE 3G3RV High function General purpose Inverters Cat No I532 E1 1...
Страница 36: ...1 22...
Страница 106: ...3 14...
Страница 126: ...4 20...
Страница 216: ...5 90...
Страница 388: ...7 26...